Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Bit
Meaning
Note:
The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).
6
Enable speed setpoint
7
Acknowledge fault
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
8
reserved
9
reserved
10
Master ctrl by PLC
Note:
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via STW1.9 = "1"..
11
Direction reversal
12
Reserved
13
Motorized potentiometer, setpoint, raise
14
Motorized potentiometer, lower setpoint
Note:
If motorized potentiometer setpoint raise and lower are 0 or 1 simultaneously, the current setpoint is frozen.
15
reserved
STW1 (control word 1), positioning mode, p0108.4 = 1
See function diagram [2475]
Table 10-5
Description of STW1 (control word 1), positioning mode
Bit
Meaning
0
ON/OFF1
356
Comments
1
Enable setpoint
0
Inhibit setpoint
Set ramp-function generator input to zero
0/1
Acknowledge fault
0
No effect
-
-
-
-
1
Master ctrl by PLC
This signal must be set so that the process data
transferred via PROFIdrive is accepted and
becomes effective.
0
PLC has no master control
Process data transferred via PROFIdrive is
rejected - i.e. it is assumed to be zero.
1
Direction reversal
0
No direction reversal
1
Motorized potentiometer, setpoint, raise
0
Motorized potentiometer setpoint raise not
selected
1
Motorized potentiometer, lower setpoint
0
Motorized potentiometer setpoint lower not
selected
-
-
Comments
0/1
ON
Pulse enable possible
0
OFF1
Braking with the ramp-function generator, then
pulse cancellation and power-on inhibit.
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
BICO
BI: p1142
BI: p2103
-
-
BI: p0854
BI: p1113
BI: p1035
BI: p1036
-
BICO
BI: p0840
Drive Functions