Function modules
7.2 Technology controller
Figure 7-2
Fill level control: controller structure
Table 7-1
Key parameters for the level control
Parameter
p1155
n_setp1 downstream of RFG
p2200
BI: Technology controller enable
p2253
CI: Technology controller setpoint 1
p2263
Technology controller type
p2264
CI: Technology controller actual value
(X
ACTUAL
p2280
Technology controller p-gain
p2285
Technology controller integral action time
7.2.5

Integration

The technology controller function is integrated in the system as follows.
Function diagrams (see SINAMICS S List Manual)
● 7950 Fixed values (r0108.16 = 1)
● 7954 Motorized potentiometer (r0108.16 = 1)
● 7958 Closed-loop control (r0108.16 = 1)
Overview of key parameters (see SINAMICS S List Manual)
Fixed setpoints
● p2201[0..n] CO: Technology controller, fixed value 1
222
Designation
)
Example
p1155 = r2294 Tec_ctrl output_sig [FP 3080]
p2200 = 1 Technology controller enabled
p2253 = r2224 Fixed setpoint active [FP 7950]
p2263 = 1 D component in fault signal [FP 7958]
p2264 = r4055 [1] Analog input AI1 of TB30
p2280 Determine by optimization
p2285 Determine by optimization
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4