Internal Encoding Of The Binector/Connector Output Parameters; Sample Interconnections - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

12.4.4

Internal encoding of the binector/connector output parameters

The internal codes are required for writing BICO input parameters via PROFIBUS, for
example.
Figure 12-6
12.4.5

Sample interconnections

Example 1: Interconnection of digital signals
Suppose you want to operate a drive via terminals DI 0 and DI 1 on the Control Unit using
jog 1 and jog 2.
Figure 12-7
Example 2: Connection of OFF3 to several drives
The OFF3 signal is to be connected to two drives via terminal DI 2 on the Control Unit.
Each drive has a binector input 1. OFF3 and 2. OFF3. The two signals are processed via an
AND gate to STW1.2 (OFF3).
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Internal encoding of the binector/connector output parameters
Interconnection of digital signals (example)
Basic information about the drive system
12.4 BICO technology: interconnecting signals
481