Mitsubishi Electric MELSEC Q Series User Manual page 216

Programmabale web server module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5 CONNECTING WEB SERVER MODULE TO NETWORK
5 - 14
(b)
After writing the PLC parameters to the programmable controller CPU,
power the programmable controller off and then on or reset the CPU
module.
(c)
The settings of the Web server module are as follows.
1)
System setting
 IP address
 Subnet mask
 Connecting through LAN or the router.
 Use the default HTTP port number (80).
 Use the default FTP port number (21).
 System name: QJ71WS96
 Do not execute network diagnoses (ping).
 Automatic connection to network at start-up.
2)
Account setting
 User name
 Password
 Access authority
 Initial screen
3)
IP filter setting
 Pass the IP packet that has not been set in [Filter setting]. (Without
filter setting)
(2) Reset of switch setting of GX Developer
After setting the Web server module with the Web browser, reset the default
setting in the switch setting of GX Developer.
(a)
Write "0000
(b)
After writing the PLC parameters to the programmable controller CPU,
power the programmable controller off and then on or reset the CPU
module.
(c)
The settings made on the corresponding setting screen of the standard
screen of the Web browser are enabled.
: 192. 168. 3. 3
: 255. 255. 255. 0
:QJ71WS96 (All in uppercase)
:MITSUBISHI (All in uppercase)
:Device write/Tag component
write/Administrator
: Standard screen top page
" to Switch 2 in the switch setting of GX Developer.
H
MELSEC-Q
5 - 14

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71ws96