5 CONNECTING WEB SERVER MODULE TO NETWORK
5 - 14
(b)
After writing the PLC parameters to the programmable controller CPU,
power the programmable controller off and then on or reset the CPU
module.
(c)
The settings of the Web server module are as follows.
1)
System setting
IP address
Subnet mask
Connecting through LAN or the router.
Use the default HTTP port number (80).
Use the default FTP port number (21).
System name: QJ71WS96
Do not execute network diagnoses (ping).
Automatic connection to network at start-up.
2)
Account setting
User name
Password
Access authority
Initial screen
3)
IP filter setting
Pass the IP packet that has not been set in [Filter setting]. (Without
filter setting)
(2) Reset of switch setting of GX Developer
After setting the Web server module with the Web browser, reset the default
setting in the switch setting of GX Developer.
(a)
Write "0000
(b)
After writing the PLC parameters to the programmable controller CPU,
power the programmable controller off and then on or reset the CPU
module.
(c)
The settings made on the corresponding setting screen of the standard
screen of the Web browser are enabled.
: 192. 168. 3. 3
: 255. 255. 255. 0
:QJ71WS96 (All in uppercase)
:MITSUBISHI (All in uppercase)
:Device write/Tag component
write/Administrator
: Standard screen top page
" to Switch 2 in the switch setting of GX Developer.
H
MELSEC-Q
5 - 14