9 TROUBLE SHOOTING
Error
Error name
code
Access target CPU
0607h
setting file error
Component setting
0609h
error
Component device
060Ah
error
060Bh
Logging setting error
CPU event setting
060Dh
error
060Eh
Tag event setting error
Time/Interval event
060Fh
setting error
Access target CPU
0610h
setting error
0611h
File open error
9 - 28
Error definition
The access target CPU setting file
is missing or destroyed.
Bits were specified for a word
device in the component setting.
The device name specified in the
component setting is incorrect, or
an unusable device was specified.
The logging setting file is
destroyed.
The event setting file is destroyed.
The event setting file is destroyed.
The event setting file is destroyed.
The data of the network path of
the access target CPU setting is
destroyed.
At start-up or setting update, the
following was detected.
 Failed to open the logging file or
event history file.
At other than start-up or setting
update, the following was
detected.
 Failed to open the logging file or
event history file.
(From the previous page)
Corrective action
 After initializing the module (refer
to Section 4.13), make the
access target CPU setting (refer
to Section 4.6.7) again.
 Check the component setting.
(Refer to Section 6.3.3)
 Check the device of the
component setting. (Refer to
Section 6.3.3)
 After initializing the module (refer
to Section 4.13), perform the
logging setting (refer to Section
6.4.5) again.
 After initializing the module (refer
to Section 4.13), perform the
CPU event setting (refer to
Section 6.5.3) again.
 After initializing the module (refer
to Section 4.13), perform the tag
event setting (refer to Section
6.5.3) again.
 After initializing the module (refer
to Section 4.13), perform the
time/interval event setting (refer
to Section 6.5.3) again.
 After initializing the module (refer
to Section 4.13), perform the
access target CPU setting (refer
to Section 4.6.7) again.
 By FTP operation (refer to
Section 6.7), delete unnecessary
files to secure a free space in the
standard ROM.
 Check the CF card. (Refer to
Section 9.1 (9).)
(Continued on the next page)
MELSEC-Q
Error type
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Continue
9 - 28