9 TROUBLE SHOOTING
Error
Error name
code
0067h
Data receive error
0080h
Read size error
0081h
Device type error
0082h
Device number error
0083h
Device point error
0084h
Write size error
0085h
Link parameter error
0087h
0088h
System error
0089h
RUN time disable
00D2h
error
00D4h
System error
Receive data length
00D7h
error
00D8h
Protocol error
00D9h
Address error
00DBh
Write error
00E0h
Station No. error
00E1h
Processing mode error
Intelligent function
00E2h
module specification
error
00E3h
Other data error
00E4h
Link specification error
00E8h
System error
00E9h
Link time-out
9 - 19
Error definition
Failed to receive data.
The read size is abnormal.
The specified device type is
invalid.
The specified device number is
outside the range.
The number of device points is
abnormal.
The write size is abnormal.
The link parameters are
destroyed.
A request disabled during RUN
time was issued.
The receive data length or byte
length is outside the range.
The communication procedure is
improper.
The address is abnormal.
Data cannot be written.
The specified station No. does not
exist.
A request invalid for the access
target CPU was sent.
The specified intelligent (special)
function module is faulty.
Request data is erroneous.
The request sent to the link
module on the access route is
invalid. (Unsupported access
route)
The link interruption has occurred
at the access target during
processing.
(From the previous page)
Corrective action
 Check the CPU in the access path.
 Check the CPU in the access path.
 Check the device type entered in
device monitor or component
setting.
 Check the device No. entered in
device monitor or component
setting.
 Check the CPU in the access path.
 Check the CPU in the access path.
 Re-set the link parameters for
programmable controller CPUs on
the access route.
 System error ( 1)
 Check the CPU in the access path.
 System error ( 1)
 Check the cables connected on
the access route.
 Check the cables connected on
the access route.
 Check the CPU in the access path.
 Check the CPU in the access path.
 Check the station No. setting in the
access target CPU setting. (Refer
to Section 4.6.7)
 Check "PLC series" in the access
target CPU setting.
(Refer to Section 4.6.7)
 Check the "U \G " of the buffer
memory specified in Device
monitor or Component setting.
 Check the CPU in the access path.
 Review the access route referring
to the accessible range.
(Refer to Appendix 2)
 System error ( 1)
 Make the module return to the link
on the access route.
(Continued on the next page)
MELSEC-Q
Error type
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
Continue
9 - 19