9 TROUBLE SHOOTING
Error
Error name
code
081Bh
POP server login error
Address notification
0820h
setting file error
System setting file
0830h
error
Account setting file
0831h
error
08A0h
08A1h
08A2h
08A3h
08B0h
System error
08B1h
08C0h
0900h
0901h
0902h
Non-set item error
0903h
Write authority error
Outside setting range
0904h
error
No specified
0905h
component error
Device specification
0906h
error
Device write disable
0907h
(device test) error
9 - 42
Error definition
Failed to connect to the mail
server (POP server).
The address notification setting file
is missing or destroyed.
The system setting file is missing
or destroyed.
The account setting file is missing
or destroyed.
An item that has not been set was
specified.
The user who does not have write
authority attempted to write.
A value outside the setting range
was specified.
The component specified in the
data does not exist.
An incorrect device (that cannot
be handled) was specified.
Execution of the device test was
attempted when Device write
disable request (YA) is on.
(From the previous page)
Corrective action
 Check the e-mail setting.
(Refer to Section 6.3.3)
 Check the connection with the
mail server.
 Power on the programmable
controller a few minutes after
power-off.
 After initializing the module (refer
to Section 4.13), perform the
address notification setting (refer
to Section 6.9.2) again.
 After initializing the module (refer
to Section 4.13), perform the
system setting (refer to Section
4.6.3) again.
 After initializing the module (refer
to Section 4.13), perform the
account setting (refer to Section
4.6.5) again.
 System error ( 1)
 Check the setting and execute
again.
 Log in with the account with write
authority, and execute again.
 Check the setting and execute
again.
 Check the setting and execute
again.
 Check the setting and execute
again.
 Turn off Device write disable
request (YA) and execute again.
(Continued on the next page)
MELSEC-Q
Error type
Continue
Stop
Stop
Stop
Stop
Display
Display
Display
Display
Display
Display
Display
9 - 42