The current actual temperature used by the device can be cyclically transmitted to the bus.
2.21.84 Temperature reading — Difference of value for sending the actual temperature (x 0.1°C)
Options:
If the change in temperature exceeds the parameterised difference between the measured
actual temperature and the previous actual temperature that was sent, the changed value will
be transmitted.
Note
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
2.21.85 Temperature reading — Adjustment value for internal temperature measurement (x
0.1°C)
Options:
Every installation location has different physical conditions (interior or exterior wall, lightweight
or solid wall, etc.). In order to use the actual temperature at the installation location as a
measured value for the device, a temperature measurement must be performed by an external
equalised and / or calibrated thermometer at the installation location. The difference between
the actual temperature displayed on the device and the actual temperature determined by the
external measurement device must be entered in the parameter field as an "Adjustment value".
Note
 
Product manual 2CKA001473B5023
Control elements and application parameter
Setting option between 1 - 100
Setting option between 1 - 100
The calibration measurement should not be carried out immediately after the
device has been installed. The device should first adjust to the ambient
temperature before calibration is carried out. The calibration measurement
should be repeated shortly before or after the room is occupied.
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
Application "Internal RTC"