2.21.106 Setpoint settings — Hysteresis for switchover heating/cooling (x 0.1°C)
Options:
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling. If the
room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating.
Note
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
2.21.107 Setpoint settings — Setpoint temperature for heating and cooling comfort (°C)
Options:
Specifies the comfort temperature for heating and cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
2.21.108 Temperature reading — Operating mode for fault
Options:
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently specify the heating/cooling operating type. As a result, the operating type
best suited to protecting the building will be selected.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
Note
The following parameter is available when the "Control function" parameter is
set on "Heating and cooling with additional stages".
The same parameter is available which is also available when the "Control
function" parameter is set on "Heating and cooling".
 
Product manual 2CKA001473B5023
Control elements and application parameter
Setting option between 5 - 100
Setting option between 10 - 40
Cooling
Heating
Application "Internal RTC"
│176