Diagnostics; Programmable Analog Output; Settings - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Parameter
8420, 8425,
8426
8430, 8435, 8436
...
8490, 8495, 8496

Diagnostics

Actual signal
0120,
0121
1401
1402/1403/1410
Alarm
AI1 LOSS
/
AI2 LOSS
Fault
AI1 LOSS
/
AI2 LOSS
PAR AI SCALE

Programmable analog output

One programmable current output (0...20 mA) is available. Analog output signal can
be inverted, filtered and the maximum and minimum values can be adjusted. The
analog output signals can be proportional to motor speed, output frequency, output
current, motor torque, motor power, etc. The update cycle for the analog output is
2 ms.
Analog output can be controlled with Sequence programming. It is also possible to
write a value to an analog output through a serial communication link.

Settings

Parameter
Group
15 ANALOG OUTPUTS
Group
35 MOTOR TEMP MEAS
8423/8433/.../8493
Diagnostics
Actual signal
0124
0170
Fault
Additional information
AI as Sequence programming reference or trigger
signal
Additional information
Analog input values
AI1/A2 signal loss through RO 1
AI1/A2 signal loss through RO 2...4. With option
MREL-01 only.
AI1/AI2 signal below limit
3022 AI2 FAULT LIMIT
AI1/AI2 signal below limit
3022 AI2 FAULT LIMIT
Incorrect AI signal scaling
1304)
Additional information
AO value selection and processing
AO in motor temperature measurement
AO control with Sequence programming
Additional information
AO value
AO control values defined by Sequence programming
Program features 131
3021 AI1 FAULT LIMIT
3021 AI1 FAULT LIMIT
(1302
<
1301
or
1305
/
/
<