3-wire macro

This macro is used when the drive is controlled using momentary push-buttons. It
provides three constant speeds. To enable the macro, set the value of parameter
9902 APPLIC MACRO
For the parameter default values, see section
page 176. If you use other than the default connections presented below, see section
I/O terminals
on page 51.
Note: When the stop input (DI2) is deactivated (no input), the control panel start and
stop buttons are disabled.

Default I/O connections

1...10 kohm
max. 500 ohm
1)
See parameter group
SPEEDS:
DI3 DI4 Operation (parameter)
0
0
Set speed through AI1
1
0
Speed 1 (1202)
0
1
Speed 2 (1203)
1
1
Speed 3 (1204)
to 2 (3-WIRE).
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Motor speed reference: 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Motor speed value: 0...20 mA
8
GND
Analog output circuit common
2)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Start (pulse
13 DI2
Stop (pulse
14 DI3
Forward (0) / Reverse (1)
15 DI4
Constant speed selection
16 DI5
Constant speed selection
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
12 CONSTANT
Application macros 113
Default values with different macros
)
)
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
Tightening torque = 0.4 N·m / 3.5 lbf·in.
Safe torque off connections (X1C:STO; not
shown in the diagram) are jumpered by default.
1)
1)
on