Connection examples of two-wire and three-wire sensors
Hand/Auto, PID control, and Torque control macros (see section
pages 116,
117
and 118, respectively) use analog input 2 (AI2). The macro wiring
diagrams on these pages use an externally powered sensor (connections not shown).
The figures below give examples of connections using a two-wire or three-wire
sensor/transmitter supplied by the drive auxiliary voltage output.
Note: Maximum capability of the auxiliary 24 V (200 mA) output must not be
exceeded.
Two-wire sensor/transmitter
-
4...20 mA
P
+
I
Note: The sensor is supplied through its current output and the drive feeds the supply
voltage (+24 V). Thus the output signal must be 4...20 mA, not 0...20 mA.
Three-wire sensor/transmitter
OUT
(0)4...20 mA
P
-
I
+
X1A
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
GND
...
9
+24V Auxiliary voltage output, non-isolated,
+24 V DC, max. 200 mA
10
GND
X1A
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
GND
...
9
+24V Auxiliary voltage output, non-isolated,
+24 V DC, max. 200 mA
10
GND