System Controls - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/Value
1505 MAXIMUM
AO1
0.0...20.0 mA
1506 FILTER AO1
0.0...10.0 s
16 SYSTEM
CONTROLS
1601 RUN ENABLE
NOT SEL
DI1
DI2
DI3
DI4
DI5
COMM
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
1602 PARAMETER
LOCK
LOCKED
OPEN
Description
Defines the maximum value for the analog output signal AO.
See the figure for parameter
Maximum value
Defines the filter time constant for analog output AO, ie the
time within which 63% of a step change is reached. See the
figure for parameter
1303 FILTER
Filter time constant
Parameter view, Run enable, parameter lock etc.
Selects a source for the external Run enable signal.
Allows the drive to start without an external Run enable
signal.
External signal required through digital input DI1. 1 = Run
enable. If Run enable signal is switched off, the drive will not
start or coasts to stop if it is running.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Fieldbus interface as the source for inverted Run enable
signal (Run disable), ie control word
1
bit 6 (with ABB drives profile
control word is sent by the fieldbus controller through the
fieldbus adapter or embedded fieldbus (Modbus) to the
drive. For the control word bits, see sections
communication profile
communication profile
External signal required through inverted digital input DI1. 0
= Run enable. If Run enable signal is switched on, the drive
will not start or coasts to stop if it is running.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Selects the state of the parameter lock. The lock prevents
parameter changing from the control panel.
Parameter values cannot be changed from the control
panel. The lock can be opened by entering the valid code to
parameter
1603 PASS
The lock does not prevent parameter changes made by
macros or fieldbus.
The lock is open. Parameter values can be changed.
Actual signals and parameters 203
1502 AO1 CONTENT
AI1.
0301 FB CMD WORD
5319 EFB PAR 19
on page
320
and
ABB drives
on page 315.
CODE.
Def/FbEq
20.0 mA
MIN.
1 =
0.1 mA
0.1 s
1 = 0.1 s
NOT SEL
0
1
2
3
4
5
7
bit 3). The
DCU
-1
-2
-3
-4
-5
OPEN
0
1