Actual signals
No.
Name/Value
0309 ALARM WORD
2
04 FAULT HISTORY Fault history (read-only)
0401 LAST FAULT
0402 FAULT TIME 1 Day on which the latest fault occurred.
Description
Bit 2 =
UNDERVOLTAGE
Bit 3 =
DIR LOCK
Bit 4 =
IO COMM
Bit 5 =
AI1 LOSS
Bit 6 =
AI2 LOSS
Bit 7 =
PANEL LOSS
Bit 8 =
DEVICE OVERTEMP
Bit 9 =
MOTOR TEMP
Bit 10 =
UNDERLOAD
Bit 11 =
MOTOR STALL
Bit 12 =
AUTORESET
Bit 13...15 = Reserved
A 16-bit data word. For the possible causes and remedies
and fieldbus equivalents, see chapter
335.
An alarm can be reset by resetting the whole alarm word:
Write zero to the word.
Bit 0 = Reserved
Bit 1 =
PID SLEEP
Bit 2 =
ID RUN
Bit 3 = Reserved
Bit 4 =
START ENABLE 1 MISSING
Bit 5 =
START ENABLE 2 MISSING
Bit 6 =
EMERGENCY STOP
Bit 7 =
ENCODER ERROR
Bit 8 =
FIRST START
Bit 9 =
INPUT PHASE LOSS
Bit 10...11 = Reserved
Bit 12 =
MOTOR BACK EMF
Bit 13 =
SAFE TORQUE OFF
Bit 14...15 = Reserved
Code of the latest fault. See chapter
335
for the codes. 0 = Fault history is clear (on panel display
= NO RECORD).
Format: Date if the real time clock is operating. / The
number of days elapsed after the power-on if the real time
clock is not used, or was not set.
Actual signals and parameters 183
Fault tracing
on page
Fault tracing
on page
FbEq
1 = 1
1 = 1
days