148 Program features
Power limit
Power limitation is used to protect the input bridge and the DC intermediate circuit.
If the maximum allowed power is exceeded, the drive torque is automatically limited.
Maximum overload and continuous power limits depend on the drive hardware.
For specific values, see chapter
Automatic resets
The drive can automatically reset itself after overcurrent, overvoltage, undervoltage,
external and "analog input below a minimum" faults. The Automatic resets must be
activated by the user.
Settings
Parameter
Group
31 AUTOMATIC RESET
Diagnostics
Alarm
AUTORESET
Supervisions
The drive monitors whether certain user selectable variables are within the user-
defined limits. The user may set limits for speed, current etc. The supervision status
can be indicated through relay or digital output.
The supervision functions operate on a 2 ms time level.
Settings
Parameter group
32 SUPERVISION
Diagnostics
Actual signal
1401
1402/1403/1410
1805
8425,
8426
/ 8435, 8436 /.../8495,
8496
Technical data
on page 357.
Additional information
Automatic reset settings
Additional information
Automatic reset alarm
Additional information
Supervision status through RO 1
Supervision status through RO 2...4. With option
MREL-01 only.
Supervision status through DO
Sequence programming state change according to
supervision functions