Alarm Messages Generated By The Drive - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Alarm messages generated by the drive

CODE ALARM
2001
OVERCURRENT
0308
bit 0
(programmable fault
function 1610)
2002
OVERVOLTAGE
0308
bit 1
(programmable fault
function 1610)
2003
UNDERVOLTAGE
0308
bit 2
(programmable fault
function 1610)
2004
DIR LOCK
0308
bit 3
2005
IO COMM
0308
bit 4
(programmable fault
function 3018, 3019)
2006
AI1 LOSS
0308
bit 5
(programmable fault
function 3001, 3021)
2007
AI2 LOSS
0308
bit 6
(programmable fault
function 3001, 3022)
CAUSE
Output current limit
controller is active.
DC overvoltage
controller is active.
DC undervoltage
controller is active.
Change of direction is
not allowed.
Fieldbus
communication break
Analog input AI1 signal
has fallen below limit
defined by parameter
3021 AI1 FAULT
LIMIT.
Analog input AI2 signal
has fallen below limit
defined by parameter
3022 AI2 FAULT
LIMIT.
Fault tracing 337
WHAT TO DO
Check motor load.
Check acceleration time
2205).
Check motor and motor cable
(including phasing).
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C.
See section
Derating
Check deceleration time
2206).
Check input power line for static or
transient overvoltage.
Check input power supply.
Check parameter
1003 DIRECTION
settings.
Check status of fieldbus
communication. See chapter
control with embedded fieldbus
page 301, chapter
Fieldbus control
with fieldbus adapter
appropriate fieldbus adapter manual.
Check fault function parameter
settings.
Check connections.
Check if master can communicate.
Check fault function parameter
settings.
Check for proper analog control signal
levels.
Check connections.
Check fault function parameter
settings.
Check for proper analog control signal
levels.
Check connections.
(2202
and
on page 359.
(2203
and
Fieldbus
on
on page
325
or