334 Fieldbus control with fieldbus adapter

Fieldbus reference scaling

Fieldbus references REF1 and REF2 are scaled for the DCU profile as shown in the
following table.
Note: Any correction of the reference (see section
correction
on page 332) is applied before scaling.
Reference Range
REF1
-214783648
...
+214783647
REF2
-214783648
...
+214783647
Note: The settings of parameters
effect on the reference scaling.

Reference handling

Reference handling is the same for the ABB drives profile (embedded fieldbus) and
DCU profile. See section

Actual value scaling

The scaling of the integers sent to the master as Actual values depends on the
selected function. See chapter
Reference
Scaling
type
Speed or
1000 = 1 rpm / 1 Hz
frequency
Speed or
1000 = 1%
frequency
Torque
1000 = 1%
PID
1000 = 1%
reference
1104 REF1 MIN
Reference handling
Actual signals and parameters
Reference selection and
Remarks
Final reference limited by
1104/1105. Actual motor speed
limited by
2007/2008
Final reference limited by
1107/1108. Actual motor speed
limited by
2007/2008
Final reference limited by
2015/2017
2016/2018
Final reference limited by
4012/4013
4112/4113
and
1107 REF2 MIN
on page 311.
on page 175.
2001/2002
(speed) or
(frequency).
2001/2002
(speed) or
(frequency).
(torque 1) or
(torque 2).
(PID set 1) or
(PID set 2).
have no