ABB ACS355 User Manual page 67

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Select the application macro according to which the
control cables are connected.
Continue with the application set-up. After completing
a set-up task, the Start-up assistant suggests the next
one.
OK
• Press
(when
continue with the suggested task.
• Press key
OK
to move to the following task without doing the
suggested task.
EXIT
• Press
to stop the Start-up assistant.
DIRECTION OF THE MOTOR ROTATION
Press key
to switch to local control (LOC shown
LOC
REM
on the left).
• If the drive is in remote control (REM shown on the
status line), switch to local control by pressing
• If you are not in the Output mode, press
repeatedly until you get there.
• Increase the frequency reference from zero to a
small value with key
• Press
to start the motor.
• Check that the actual direction of the motor is the
same as indicated on the display ( means forward
and
reverse).
• Press
to stop the motor.
To change the direction of the motor rotation:
• Invert the phases by changing the value of
parameter
9914
1 (YES), or vice versa.
• Verify your work by applying input power and
repeating the check as described above.
After the whole set-up is completed, check that there
are no faults or alarms shown on the display and the
panel LED is green and does not blink.
is highlighted) to
Continue
to highlight
and then press
Skip
.
to the opposite, ie from 0 (NO) to
FINAL CHECK
The drive is now ready for use.
Start-up, control with I/O and ID run 67
REM
9902 APPLIC MACRO
ABB STANDARD
[1]
EXIT
REM
Do you want to
continue with
EXT1 reference setup?
Continue
Skip
EXIT
LOC
.
LOC
REM
EXIT
DIR
forward
direction
LOC
9914 PHASE INVERSION
[1]
CANCEL
PAR EDIT
00:00
SAVE
CHOICE
00:00
OK
xx.xHz
xx x Hz
.
x
.
x A
xx x %
.
00:00
MENU
reverse
direction
PAR EDIT
YES
00:00
SAVE