280 Actual signals and parameters
All parameters
No.
Name/Value
5318 EFB PAR 18
0...65535
5319 EFB PAR 19
0000...FFFF
hex
5320 EFB PAR 20
0000...FFFF
hex
54 FBA DATA IN
5401 FBA DATA IN 1 Selects data to be transferred from the drive to the fieldbus
0
1...6
101...9999
5402 FBA DATA IN 2 See
...
...
5410 FBA DATA IN
10
55 FBA DATA OUT
5501 FBA DATA
OUT 1
0
Description
For Modbus: Sets an additional delay before the drive
begins transmitting response to the master request.
Delay in milliseconds
ABB drives profile
(ABB DRV LIM
Control word. Read only copy of the fieldbus Control word.
Control word
ABB drives profile
(ABB DRV LIM
Status word. Read only copy of the fieldbus Status word.
Status word
Data from the drive to the fieldbus controller through a
fieldbus adapter. See chapter
adapter
on page 325.
Note: In adapter module the parameter group number is 3.
controller.
Not in use
Control and status data words
5401 setting
1
2
3
4
5
6
Parameter index
5401 FBA DATA IN
...
See
5401 FBA DATA IN
Data from the fieldbus controller to the drive through a
fieldbus adapter. See chapter
adapter
on page 325.
Note: In adapter module the parameter group number is 2.
Selects data to be transferred from the fieldbus controller to
the drive.
Not in use
or
ABB DRV
or
ABB DRV
Fieldbus control with fieldbus
Data word
Control word
REF1
REF2
Status word
Actual value 1
Actual value 2
1.
1.
Fieldbus control with fieldbus
Def/FbEq
0
1 = 1
FULL)
0000 hex
FULL)
0000 hex