328 Fieldbus control with fieldbus adapter
The new settings will take effect when the drive is next powered up, or when
parameter
5127 FBA PAR REFRESH

Drive control parameters

After the fieldbus communication has been set up, the drive control parameters listed
in the table below should be checked and adjusted where necessary.
The Setting for fieldbus control column gives the value to use when the fieldbus
interface is the desired source or destination for that particular signal. The
Function/Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
1001 EXT1
COMMANDS
1002 EXT2
COMMANDS
1003
DIRECTION
1010 JOGGING SEL COMM
1102 EXT1/EXT2
SEL
1103 REF1 SELECT
1106 REF2 SELECT
OUTPUT SIGNAL SOURCE SELECTION
1401 RELAY
OUTPUT 1
1501 AO1 CONTENT
SEL
SYSTEM CONTROL INPUTS
1601 RUN ENABLE
is activated.
Setting for
fieldbus control
COMM
COMM
FORWARD
REVERSE
REQUEST
COMM
COMM
COMM+AI1
COMM*AI1
COMM
COMM+AI1
COMM*AI1
COMM
COMM(-1)
135 (ie
0135
COMM VALUE
1)
COMM
Function/Information
Selects the fieldbus as the source for the start
and stop commands when EXT1 is selected as
the active control location.
Selects the fieldbus as the source for the start
and stop commands when EXT2 is selected as
the active control location.
Enables the rotation direction control as defined
by parameters
1001
control is explained in section
handling
on page 311.
Enables jogging 1 or 2 activation through the
fieldbus.
Enables EXT1/EXT2 selection through the
fieldbus.
Fieldbus reference REF1 is used when EXT1 is
selected as the active control location. See
section
Reference selection and correction
page 332.
Fieldbus reference REF2 is used when EXT2 is
selected as the active control location. See
section
Reference selection and correction
page 332.
Enables relay output RO control by signal
COMM RO
WORD.
Directs the contents of fieldbus reference
COMM VALUE 1
to analog output AO.
Selects the fieldbus interface as the source for
the inverted Run enable signal (Run disable).
and 1002. The direction
Reference
on
on
0134
0135