184 Actual signals and parameters
Actual signals
No.
Name/Value
0403 FAULT TIME 2 Time at which the latest fault occurred.
0404 SPEED AT FLT Motor speed in rpm at the time the latest fault occurred
0405 FREQ AT FLT
0406 VOLTAGE AT
FLT
0407 CURRENT AT
FLT
0408 TORQUE AT
FLT
0409 STATUS AT
FLT
0412 PREVIOUS
FAULT 1
0413 PREVIOUS
FAULT 2
0414 DI 1-5 AT FLT
Description
Format on the assistant control panel: Real time (hh:mm:ss)
if the real time clock is operating. / Time elapsed after the
power-on (hh:mm:ss minus the whole days stated by signal
0402 FAULT TIME
1) if real time clock is not used, or was
not set.
Format on the basic control panel: Time elapsed after
power-on in 2 second ticks (minus the whole days stated by
signal
0402 FAULT TIME
value 514 equals 17 minutes and 8 seconds (= 514/30).
Frequency in Hz at the time the latest fault occurred
Intermediate circuit voltage in V DC at the time the latest
fault occurred
Motor current in A at the time the latest fault occurred
Motor torque in percent of the motor nominal torque at the
time the latest fault occurred
Drive status in hexadecimal format at the time the latest
fault occurred
Fault code of the 2nd latest fault. See chapter
on page
335
for the codes.
Fault code of the 3rd latest fault. See chapter
on page
335
for the codes.
Status of digital inputs DI1...5 at the time the latest fault
occurred (binary).
Example: 10000 = DI1 is on, DI2...DI5 are off.
1). 30 ticks = 60 seconds. Eg
Fault tracing
Fault tracing
FbEq
1 = 2 s
1 = 1 rpm
1 = 0.1 Hz
1 = 0.1 V
1 = 0.1 A
1 = 0.1%
1 = 1
1 = 1