Service Current Rating

Service Current Rating
The input current rating of the DC power supply equipment shall be considered
when selecting the AC main service.
The DC power system has normal loads and start-up loads. These loads are dependent on the number
of Base Radios in the site and the size and condition of the backup battery system. The normal
load of a typical power system is provided in
using battery backup.
Cabinets. These loads may differ for the customer designed power systems.
Table 3-4 Typical Power Loads and Heat Dissipation Values - MTS UHF Configurations
MTS UHF
Configuration
TETRA TX 10 W
MTS2 with 1 BR
MTS2 with 1 BR w.
Hybrid
MTS2 with 2 BRs
MTS2 with 2 BRs w.
Hybrid
MTS4 with 1 BR w.
MTCC/ATCC
MTS4 with 2 BRs w.
MTCC/ATCC
3-16
rated min. 20 A/55 VDC should be introduced. And for the MTS4, two of these
units should be used, one for each of the two incoming DC lines. Alternatively
for the MTS4, one relay rated 40 A/55 VDC can be used if the two DC lines are
connected to one battery pack. The relays should be controlled in a way that they
disconnect the batteries once the voltage drops below 40.5 V, where the PSU in
the MTS shuts down. Two Motorola kits are available for this purpose:
• MTS2 LVD RELAY RETROFIT KIT (Kit Number: GMDN2206A)
• MTS4 LVD RELAY RETROFIT KIT (Kit Number: GMDN2207A)
The battery installation need a short circuit protection closest to the batteries.
The batteries should be installed in the same building and properly ventilated.
Table 3-5
lists typical power loads and heat dissipation values for Expansion
Heat
AC
AC
(W)
(W)
140
130
165
155
245
225
295
275
240
230
375
355
Table 3-4
for several common MTS configurations
AC
Heat AC
When
When
Charg-
Charging
ing (W)
(W)
520
185
545
210
625
280
675
330
625
290
755
410
Chapter 3: Site Preparation
DC
Heat
-48 V
DC
(W)
(W)
Comment
135
125
No combining, low
power PA, no fans
160
150
Low power PA, no
fans
240
220
Two TX ant., low
power PA, no fans
285
265
Low power PA, no
fans
235
225
Low power PA,
fans
365
345
Low power PA,
fans
6802800U74-N September 2009