Electric Characteristics - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

8.

ELECTRIC CHARACTERISTICS

Rated Value
Power Supply
HP
Model name
Hz
4
AJ  A40LALH
50
5
AJ  A45LALH
50
6
AJ  A54LALH
50
Select the breaker based on MCA of the table above.
Select the wire diameter based on the larger value of MCA or TOCA of the table above and select
a wire diameter which withstands the breaker capacity.
*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with the regional cable
standard.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
RLA : Rated Load Amp of compressor under the standard condition.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MSC : Max Starting Current
TOCA : Total Value of Each Over Current Set
MFA : Main Fuse (Circuit Breaker) Current
Full Load Characteristics
Voltage
MCA
TOCA
MSC
(V)
(A)
(A)
(A)
230
30.3
29.5
29.5
230
30.3
29.5
29.5
230
30.3
29.5
29.5
- (03 - 12) -
Electric Characteristics
Wiring Specifications *1
Limited
Power
Earth
MFA
Wiring
Cable
Cable
(A)
Length
2
2
(mm
)
(mm
)
(m) *2
32
6
4
18
32
6
4
18
32
6
4
18
Outdoor Fan
Compressor
Motor
RLA
Output
FLA
(A)
(W)
(A)
24
100
0.66
24
100
0.66
24
100
0.66