Fujitsu AIRSTAGE J-II Design & Technical Manual page 407

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2. For connecting group remote controller(s)
FEATURES
Up to a total of 16 network convertors, Central remote controller and Touch panel controller
can be connected in one VRF network system.
Four group remote controllers can be connected to one network convertor.
Two refrigerant systems can be covered by one network convertor.
SYSTEM DIAGRAM
VRF Network
ELECTRICAL WIRING
Transmission Line
1Ø 50/60 Hz
208-240 V
SWITCH
RC line
to RC
RC line to
indoor unit
Transmission line
NOTES:
Do not bind the power cable and remote controller cable to avoid an erroneous operation.
Use shield cable for transmission line and remote controller line. The shield metal should be grounded.
Use ground wire to ground the network convertor.
Network Convertor
(UTY-VGGXZ1)
to VRF System
FUSE (3 A)
X1
L
N
TRANSMISSION
POWER
Power Supply
NETWORK CONVERTOR
Power
supply
- (05 - 103) -
Group Remote Controllers (Max. 4 sets)
Transmission Line
to VRF System
L1
L3
X2
Y1 Y2 Y3 J1
J2 J3
REMOTE INDOOR UNIT
REMOTE CONTROLLER LINE
or
L1
L2
Y1 Y2 Y3 J1
J2 J3
REMOTE INDOOR UNIT
REMOTE CONTROLLER LINE
Group Remote Controller
L2
L4
Total remote controller cable
length L1+L2+L3+L4 <
It is recommended to use a
terminal box when there is
wring junction.
L3
L4
100 m
=

Advertisement

Table of Contents
loading