Model Line Up - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2.

MODEL LINE UP

2-1.
OUTDOOR UNIT
LINE UP
Capacity (kW)
HP
Cooling
Heating
4
12.1
13.6
5
14.0
16.0
6
15.5
18.0
1 : 1.1 kW cooling capacity indoor unit (Ex. AUXB04) is NOT connected.
If indoor unit whose cooling capacity is 1.1 kW is connected, calculate the value according to the following
restrictions.
Indoor unit connectable cooling capacity range
1.1 kW cooling capacity
indoor unit is NOT
connected
50% to 130%
46% to 130%
(only AJ*A40LALH)
Maximum connectable
Model name
indoor unit
AJ  A40LALH
AJ  A45LALH
AJ  A54LALH
1.1 kW cooling capacity indoor unit is connected
9.0 kW or larger cooling capacity
AU or AR is NOT connected
50% to 120%
46% to 120%
(only AJ*A40LALH)
- (02 - 02) -
Indoor unit connectable
cooling capacity (kW) *1
7
5.6 to 15.7
8
7.0 to 18.2
9
7.8 to 20.1
9.0 kW or larger cooling capacity
AU or AR is connected
50% to 110%
46% to 110%
(only AJ*A40LALH)