Fujitsu AIRSTAGE J-II Design & Technical Manual page 431

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

EXAMPLE
Application
When controlling
MODE0
the individual
P1: Arbitrary
operation states
operation state
with two external
Contact OFF→ON
contact
P2: Arbitrary
operation state
Contact OFF→ON
Others setting are
arbitrary.
When
MODE1
controlling
P1 : Arbitrary
operation by
operation state
ON or OFF of
P2 : Arbitrary
an external
operation state
contact switch
Others setting are
arbitrary.
When operating
MODE1 or 0
in the state set
P1 : SETBACK
when an external
P2 : Arbitrary
contact switch
operation state
was set to ON
and returning
Others setting are
to the original
arbitrary.
operation state
when the switch
was set to OFF
When operated in
MODE1 or 0
the state when an
P1 : Arbitrary
external contact
operation state
switch was set to
P2 : SETBACK
OFF and returned
to original
Others setting are
operation state
arbitrary.
When a
MODE2
temperature sensor
P1 : ON, COOL or
switch is connected
HEAT
and cooling and
P2 : ON, COOL or
heating switching is
HEAT
performed.
Operation conditions:
Unit operationg only
Others setting are
arbitrary.
When preventing
MODE1
chattering noise
Delay-time setting:
within 1 minute of
Delay
the external contact
P1 : Arbitrary
switch.
operation state
P2 : Arbitrary
operation state
Others setting are
arbitrary.
Setting
Wiring
Indoor
unit
External
SW controller
Indoor
unit
External
SW controller
Indoor
unit
External
SW controller
Indoor
unit
External
SW controller
Thermal sensor SW
An external switch controller
is connected to all the indoor
units of the same refrigerant
system and cooling and
heating are switched by one
temperature sensor.
Indoor
unit
External
SW controller
- (05 - 127) -
P1 : ON, COOL, 26°C P2 : OFF
SW1 ON
OFF
SW2 ON
OFF
External
contact 1
Operation state
External
contact 2
OFF
P1 : OFF P2 : ON, COOL, 26°C
SW1 ON
OFF
Operation state
External
OFF
contact 1
MODE1, P1 : SETBACK P2 : ON, COOL, 26°C
SW1 ON
OFF
Operation state
ON
External
contact 1
OFF
MODE1, P1 : ON, COOL, 26°C
P2 : When SETBACK
SW1
ON
OFF
Operation state
ON
External
contact 1
OFF
Indoor
P1 : ON, COOL, 26°C
unit
P2 : ON, HEAT, 21°C
SW1
Operation state
ON
OFF
P1 : OFF P2 : ON, COOL, 26 °C
SW1
ON
Operation state
ON
External
contact 1
OFF
Operation example
P1
P2
ON
COOL
26 °C
P2
P1
ON
COOL
26 °C
P2
P1
COOL
COOL
COOL
COOL
26 °C
26 °C
23 °C
23 °C
P1
P2
COOL
COOL
26 °C
COOL
23 °C
23 °C
ON
P2
P1
OFF
HEAT
COOL
COOL
21 °C
26 °C
23 °C
P2
P1
1min
1min
COOL
26 °C