WIRING SPECIFICATIONS
Use
Maximum 1.25 mm
Power supply cable
Minimum 0.5 mm
Transmission cable
Fuse capacity
Always ground the unit
TOTAL SYSTEM CONFIGURATION LAYOUT
XIF file
(VRF)
Register Information
PC
Tool for network
Load Information
convertor
(Software)
00 00
Outdoor unit address
Refrigerant circuit address
00 00 00
00 01 01
Group
Remote controller address
Indoor unit address
Making XIF of Network Convertor using a Tool
for network convertor (Software) provided by
Fujitsu General.
(Job is done by Network Integrator)
PCB FOR NETWORK CONVERTOR (UTY-VLGX)
PC Control
port
Jumper for
Battery On/Off
MODE switch
(SW 3)
Size
2
60245 IEC 57 or equivalent
2
LEVEL4 (NEMA) non-polar
0.33
2
mm
2 core, twisted pair solid
(22AWG)
core Shielded
3 A
Neuron ID is sent
upon pushing BMS
service switch (SW2)
UTY-VLGX
Network Convertor
(Interface for L
ON
®
VRF L
W
System
ON
ORKS
00 02 02
00 03 00
Group
VRF service switch
(SW 1)
RESET switch
SET switch
(SW 7)
(SW 4)
- (05 - 112) -
Wire type
1 ø AC208-240 V 50/60 Hz,
2-Wire + ground
(Always ground the unit)
L
ON
Network
Integration Tool
®
(e.g. LonMaker
PC
Commissioning
®
W
)
ORKS
Binding VRF with BMS
(By Network Integrator)
DC 12V IN
BMS Network
connection port
BMS service switch
(SW 2)
Remarks
®
W
compatible cable
ORKS
XIF file
)
(BMS)
BMS
®
L
W
ON
ORKS
(Open Network)
VRF Network
connection port

Advertisement

Table of Contents
loading

Table of Contents