Fujitsu AIRSTAGE J-II Design & Technical Manual page 430

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2) Connect the remote controller cable to the connecting cable, and insert it to the connector.
Set the DIP switch (SW1) to "3WIRE" on the PC board of the indoor unit.
Set to "3WIRE" the
DIP switch (SW1)
Connect to earth
Functional earthing
(ground) screw
(If necessary)
Remote controller
cable
Connecting cable
* Layout of Connector and PC board varies, depending on
the type of indoor unit
SW1
Connector
(adapter)
Indoor unit
PC board
PACKING LIST
Name and shape
Installation manual
Screw
(M4 × 16 mm)
Cable tie
WIRING SPECIFICATIONS
Use
Remote controller
cable
External input /
output cable
SPECIFICATIONS
Power supply
Dimensions [H × W × D] (mm)
Weight (g)
Indoor unit
PC board
Connector CNC01
(onboard)
Quantity
1
2
5
Size
Wire type
0.33
2
mm
Polar 3-core
22AWG
(
)
0.33
2
mm
Polar 2-core,
Twisted pair
22AWG
(
)
DC 12 V
120 × 75 × 30
- (05 - 126) -
For installing the external switch controller
For external switch controller and cable binding
Use sheathed PVC cable or shielded
cable in accordance with the regional
cable standard.
Use shielded cable in accordance with
the regional cable standard.
100
Application
Remarks

Advertisement

Table of Contents
loading