Fujitsu AIRSTAGE J-II Design & Technical Manual page 594

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2-1-2.
V-III series
SETTINGS LIST
LED105
Setting Mode
CODE No.
Pipe length
0
0
setting
Sequential start
1
0
shift
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
Height
difference
1
7
between indoor
units
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
0
0
Standard (40 to 65m)
0
1
Short (less than 40m)
0
2
Medium (65 to 90m)
0
3
Long 1 (90 to 120m)
0
4
Long 2 (120 to 165m)
0
0
Normal
0
1
21sec. Delay
0
2
42sec. Delay
0
3
63sec. Delay
0
0
Normal mode
0
1
Save energy mode 1
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Standard
0
1
Prohibited
0
2
Height difference
0
3
Prohibited
0
4
Prohibited
- (07-68) -
Outdoor unit
Factory
setting
Master Slave
l
Pipe length means the length
-
between master outdoor unit
¡
*1
and the nearest indoor unit.
The start-up timing of outdoor
l
unit (compressor) can be set
up so that it can delay several
seconds.
-
This feature is useful when
¡
*1
multiple number of outdoor units
are installed and turned on at
the same time
to limit the starting current.
l
-
¡
*1
l
-
¡
*1
l
Setting prohibited
l
If installing the indoor units (even
only one set) to a lower floor
than the outdoor unit, and the
-
height difference between the
¡
*1
indoor units is 3m or greater (i.e.,
if installing the indoor units on
separate floors), set "02 (height
difference)".
Remarks