INDOOR UNIT (setting by UTY-RNK*)
This procedure changes to the function settings used to control the indoor unit according to
●
the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the "FUNCTION SETTING" according to the
●
installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting
●
Number.
Settings will not be changed if invalid numbers or setting numbers are selected.
●
This function cannot be used on the slave units.
●
PREPARATION
1) If multiple indoor units are connected to a single wired remote controller, make sure to
manually set up the remote controller address (RC AD) on the PCBs of the indoor units.
(Refer to 1-3.)
Ex.) When four indoor units are connected
Wired
remote
controller
2) Turn on the power to the indoor unit.
●
By turning on the power indoor units initializes EEV, so make sure the piping air-tight test and
vacuuming have been conducted before turning on the power.
●
Also check again to make sure no wiring mistakes were made before turning on the power.
Breaker ON
Indoor unit
Indoor unit
Indoor unit