Address Setting - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

1-2.

ADDRESS SETTING

For this system, each address should be preset before operation.
Please refer following table for outdoor unit, indoor unit, RB unit and each remote controller.
KINDS OF ADDRESS AND SETTING RANGE
UNIT
SETTING
Refrigerant
A
circuit address
Outdoor unit
B
address *1
Outdoor unit
Number of slave
C
unit *1
Number of
L
outdoor units
installed *1
Terminal
resistor
Refrigerant
D
circuit address
Indoor unit
Indoor unit
E
address
Remote
F
controller
address
*Set up after confirming the details of each unit.
*1: This function is available VR-II, V-II and V-III series
SETTING
TYPE OF SWITCH
RANGE
Setting
00 ~ 99
example
01
0 ~ 2
0 ~ 2
1 ~ 3
ON/OFF
n Manual address setting
Setting
example
REF AD
01
n Wireless R.C
Set this switch to 00 at factory setting.
n Wired R.C. (3-wire type)
00 ~ 99
Set this switch to 00 at factory setting.
n Simple R.C.
Set this switch to 00 at factory setting.
n Wired R.C. (2-wire type)
Set this switch to 00 at factory setting.
n Automatic address setting
Set this switch to 00 at factory setting.
n Manual address setting
Setting
example
IU AD
12
n Wireless R.C
Set this switch to 00 at factory setting.
n Wired R.C. (3-wire type)
00 ~ 63
Set this switch to 00 at factory setting.
n Simple R.C.
Set this switch to 00 at factory setting.
n Wired R.C. (2-wire type)
Set this switch to 00 at factory setting.
n Automatic address setting
Set this switch to 00 at factory setting.
n Manual address setting
Setting
example
0 ~ 15
10
n Automatic address setting
Set this switch to 0 at factory setting.
- (07-03) -
Arbitrary numbers can be
REF AD
REF AD
x10
x1
SET3
SET5
See the setting method 1-6
Arbitrary numbers can be
REF AD
x10
x1
.
See the setting method 1-4-1
See the setting method 1-4-2
See the setting method 1-4-3
See the setting method 1-4-4
See the setting method 1-5-2
Arbitrary numbers can be
IU AD
x10
x1
.
See the setting method 1-4-1
See the setting method 1-4-2
See the setting method 1-4-3
See the setting method 1-4-4
See the setting method 1-5-2
RC AD
REMARKS
set in range of 00-99
DIP SW SET3-1
DIP SW SET3-2
DIP SW SET3-3
DIP SW SET3-4
(Master unit only)
DIP SW SET5-1
DIP SW SET5-2
DIP SW SET5-4
set in range of 00-99
set in range of 00-63
3-wire type R.C. can be
set in range of 0-15
2-wire type R.C. can be
set in range of 1-15
2-wire type only