Example 8 (OK)
z
Outdoor unit
Indoor unit 1
Model
Outdoor unit
AJ A54L
Indoor unit 1
AUXB04
Indoor unit 2
AUXB04
Indoor unit 3
AUXB04
Indoor unit 4
AUXB04
Indoor unit 5
AUXB04
Indoor unit 6
AUXB07
Indoor unit 7
AUXA30
*1: Condition 3: 1.1 kW cooling capacity indoor unit is connected and 9.0 kW or larger cooling capacity AU or AR
is connected.
Example 9 (Prohibited)
z
Outdoor unit
Indoor unit 1
Model
Outdoor unit
AJ A54L
Indoor unit 1
AUXB04
Indoor unit 2
AUXB04
Indoor unit 3
AUXB04
Indoor unit 4
AUXB04
Indoor unit 5
AUXB07
Indoor unit 6
AUXB07
Indoor unit 7
AUXA30
*1: Condition 3: 1.1 kW cooling capacity indoor unit is connected and 9.0 kW or larger cooling capacity AU or AR
is connected.
Capacity ratio
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Cooling
Total
Connectable indoor unit
capacity
capacity
(kW)
(kW)
15.5
15.5
1.1
1.1
50%
1.1
1.1
16.7
1.1
2.2
9.0
Capacity ratio
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Connectable indoor unit
Cooling
Total
capacity
capacity
(kW)
(kW)
15.5
15.5
1.1
1.1
50%
1.1
1.1
17.8
2.2
2.2
9.0
- (06 - 05) -
108%
capacity *1
Min.
Max.
110%
7.8
17.0
115%
capacity *1
Min.
Max.
110%
7.8
17.0
Judgement
≤ ≤
7.8 < 16.7 < 17.0 → OK
Judgement
<
17.0 < 17.8 → Prohibited