Fujitsu AIRSTAGE J-II Design & Technical Manual page 707

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

INPUT SIGNAL TYPE
The input signal type can be selected.
It is switched by Dip-Sw on the indoor unit PCB.
Dip-sw [Set 2-2]
OFF
u
ON
Note: input signal type of Ch3 (Forced thermostat off) is only "Edge".
CONTROL INPUT FUNCTION
When function setting is "Operation/Stop" mode
z
In the case of "Edge" input
Connector
Ch1 of
CNA01 or CNA02
Ch1 input of
On
CNA01 or
Off
CNA02
Operation
Indoor unit
Stop
Remote
Controller
In the case of "Pulse" input
Connector
CNA01 or CNA02
Ch1 input
CNA01
or
CNA02
Ch2 input
Indoor unit
Remote
Controller
NOTE :
The last command has priority.
The indoor units within the same remote controller group operates in the same mode.
(u...Factory setting)
Input signal type
Edge
Pulse
Input signal
Command
OFF → ON
Operation
ON → OFF
Stop
Input signal
Ch1
OFF → ON
Ch2
OFF → ON
The width of pulse must be longer than 200msec.
On
Off
On
Off
Operation
Stop
- (08 - 11) -
Edge
Pulse
On
Command
Operation
Stop
On