1-2-2.
EXTERNAL OUTPUT
●
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
●
Use an external input and output cable with appropriate external dimension, depending on the number of cables
to be installed.
●
Output voltage: Hi DC12V±2V, Lo 0V.
●
Permissible current: 50mA
Connector
External output1
Pins 1-2
External output2
Pins 1-3
CNB01
External output3
Pins 1-4
External output4
Pins 1-5
OUTPUT SELECT
When indicator etc. are connected directly
z
Operation
indicator
Error indicator
Indoor unit Fan
status indicator
connected unit
When connecting with unit equipped with a power supply
z
Connected
device 1
Connected
device 2
Connected
device 3
Heater
connected unit
Output voltage
0V
DC 12V
0V
DC 12V
0V
DC 12V
Indoor unit fan operation
0V
Auxiliary heater OFF
DC 12V
+
-
-
-
+
-
-
-
-
Relay
- (08 - 21) -
Status
Stop
Operation
Normal
Error
Indoor unit fan stop
Auxiliary heater ON
P.C.B
CNB01
1
2
3
4
5
6
P.C.B
CNB01
1
2
3
4
5
6