External Input; Optional Parts; Touch Panel Controller - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

1-4.

TOUCH PANEL CONTROLLER

External input

Control input
-
-
1-4-1.
EXTERNAL INPUT
This function performs "Emergency stop" or "All On / All Off" by using the signal to be input externally at external
input terminals.
INPUT SELECT
Use either one of these types of terminal according to the application. (Both types of terminals
cannot be used simultaneously.)
Please see more detail of selection setting by operation manual of Touch Panel Controller.
It is possible to switch to the Dry contact terminal or the Apply voltage terminal by connecting
the CN201 on the TM201 printed circuit board to the CN411 or the CN412 on the printed circuit
board of the panel side.
* The Dry contact terminal (connected to the CN411) is set when shipped from the factory.
TM201 - K1, K2
Dry contact terminal
Apply voltage terminal
Dry contact terminal TM201 (CN411)
z
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal TM201 (CN411).
*13
connected unit
*13 : Short circuit detection resistance (R
Open circuit detection resistance (R
A twisted pair cable(22AWG) should be used. Maximum length of cable is 25m.
External output
Connector
-
TM201 (CN411 or CN412)
Operation status
Error status
Connect with the CN201
CN411
CN412
P.C.B
P.C.B
K1
CH1
K2
TM201
K1
CH2
CN412
K2
(RED)
CN411
CN201
(WHITE)
) : ≤ 500 (ohm).
ON
OFF
- (08 - 29) -
External connect kit

(Optional parts)

CN410
UTY-XWZXZA
CN410
CN412
LAN
(BLACK)
(RED)
P.C.B
PANEL
) : ≥ 100 (kilo-ohm).
-
CN411
(WHITE)

Advertisement