Fujitsu AIRSTAGE J-II Design & Technical Manual page 569

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

Refrigerant circuit address setting
z
10) Pressing the "+" or "-" button, select a remote controller address (select the indoor unit you
want to operate). Then press the "ENTER" button.
11) Pressing the "+" or "-" button, display function number 02. Then press the "ENTER" button.
12) Pressing the "+" or "-" button, set up the refrigerant circuit address. (The setting range is
from 00 to 99.)
When refrigerant circuit address data was not
set up on the indoor unit (-- is displayed.)
Set up refrigerant circuit address data again.
13) Pressing the "ENTER" button to return to the address selection screen. If setting has been
completed, pressing the "MENU" button to return to the Menu 2 item selection screen.
ERROR
- (07-43) -
Remote controller address
Ex.) When setting at all the indoor units
Function number
Refrigerant circuit address
Ex.) When refrigerant circuit
address data "18" is set up
GOOD
When refrigerant circuit address data was
normally set up on the indoor unit.