Selection of pipe size
z
a
Liquid pipe
9.52
Gas pipe
19.05
12.70
Length (m)
40
Example
f
Liquid pipe
9.52
Gas pipe
15.88
12.70
Length (m)
5
Example
Limitation check
z
Total pipe length
Between outdoor unit and farthest indoor unit
Between the first separation tube and the farthest indoor unit
Between outdoor unit and the nearest indoor unit
Between outdoor unit and the first seperation tube
Calculation of additional charge refrigerant
z
1. Calculation of additional amount for pipe length
Liquid pipe size
Additional refrigerant
(kg/m)
Liquid pipe length (m)
A = (0.058 x 70) + (0.021 x 82) = 5.79 (kg)
2. Factory charged amount
Outdoor unit
B = 5.30 (kg)
3. Total refrigerant amount check
C = A + B = 5.79 + 5.30 = 11.09(kg) < 15.70 (kg) → OK
Check pipe length and height difference between units by comparing with items shown in "2-2.PIPING
LIMITATION".
a1
b
b1
6.35
9.52
6.35
19.05
12.70
15
5
10
f1
g
g1
6.35
9.52
6.35
15.88
12.70
10
5
10
9.52
6.35
0.058
0.021
70
82
Factory charged
Model
amount (kg)
AJ  A54
5.30
c
c1
d
9.52
6.35
9.52
15.88
12.70
15.88
5
10
5
h
6.35
12.70
7
Diagram
Total
a+b+c+d+e+f+g+h
b+c+d+e+f+g+h
a+a1
a
- (06 - 28) -
d1
e
e1
6.35
9.52
6.35
12.70
15.88
12.70
10
5
10
Example
Limitation
Judge
(m)
(m)
152
180m or less
OK
77
120m or less
OK
37
40m or less
OK
55
5m or more
OK
40
3m or more
OK