REFRIGERANT SYSTEM 3
Outdoor
unit
b
(16.0kW)
(13.2kW)
BP1
BP2
a1
1
(2.8kW)
Indoor
unit
System configuration
z
1
Model name
ARXD09
Capacity (kW)
2.8
System configuration
z
Outdoor unit
Model name
AJ  A54
Capacity (kW)
15.5
Capacity ratio
z
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (16.0) / (15.5) = 103.2%
*1: Condition 2: 1.1 kW cooling capacity indoor unit is connected and 9.0 kW or larger cooling capacity AU or AR
is NOT connected.
Selection of branch kit
z
Branch
Model
point No.
BP1
UTP-AX090A
BP2
UTP-AX090A
BP3
UTP-AX090A
BP4
UTP-AX090A
BP5
UTP-AX090A
BP6
UTP-AX090A
BP7
UTP-AX090A
a
c
d
(11.0kW)
(8.8kW)
BP3
BP4
b1
c1
2
3
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
(Indoor units)
2
3
4
ARXD07
ARXD07
ARXD07
2.2
2.2
2.2
(Outdoor unit)
(Within 50% to 120% *1)
Total cooling capacity of indoor units
connected downwards to the pipe.
e
f
(6.6kW)
(4.4kW)
BP5
BP6
d1
e1
4
5
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
5
6
ARXD07
ARXD07
2.2
2.2
Model
UTP-AX090A
- (06 - 27) -
g
h
(2.2kW)
(1.1kW)
BP7
f1
g1
6
7
(2.2kW)
(1.1kW)
Indoor
Indoor
unit
unit
Total Capacity
7
8
(kW)
ARXD04
ARXD04
16.0
1.1
1.1
Q'ty
7
8
(1.1kW)
Indoor
unit