SLIM DUCT / SLIM CONCEALED FLOOR TYPE
Ceiling concealed setting
z
Drain cap
Arrange the drain hose
lower than this position
Trap
Locally arranged pipe
Max.
300 mm
Horizontal or
upward gradient
Floor standing concealed setting
z
Drain cap
Install the drain pipe with downward gradient (1/50 to1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm] and connect it with adhesive (polyvinyl
chloride) so that there is no leakage.
When the pipe is long. Install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.
Drain hose
Prohibited
Rise
Gap of 1.5-2 m
Supporter
VP25
[O.D 32 mm
or more]
700 mm or less
Prohibited
Trap
- (06 - 64) -
Supporter
1.5m to 2.0m
Air bleeding
Prohibited
Air bleeding
Rise
Trap
Rise