Cont rol of the safety functions
5.3 Activation via PROFIsafe
Safety status word 2 (S_ZSW2)
S_ZSW2, input signals
see function diagram [2806].
Table 5- 6
Description of safety status word 2 (S_ZSW2)
Byte
Bi t
0
0
1
2
3
4
5
6
7
1
0
1
2
3
4
5
6, 7
2
0 ... 2
3
4, 5
6
7
3
0 ... 2
3
4
5
6
7
Signals not relevant for Basic Functions: Must not be evaluated.
1)
Only valid for CU310-2.
2)
182
Me a n i n g
STO active
SS1 active
SS2 active
SOS active
SLS active
Reserved
SLP active
Internal Event
Reserved
Active SLS level, bit 0
Active SLS level, bit 1
Reserved
SDI positive active
SDI negative active
Reserved
Reserved
SLP active position range
Reserved
Safe position valid
Safely referenced
F-DI 0 ... 2
2)
Reserved
SS2E active
SOS selected
SLP upper limit maintained
SLP lower limit maintained
R e m a rks
1
STO active
0
STO not active
1
SS1 active
0
SS1 not active
0
1)
0
1)
0
1)
0
1)
1
Internal event
0
No internal event
0
1)
0
0
1)
0
1)
0
1)
0
1)
0
1)
0
1)
0
1)
0
1)
0
1)
0
1)