Trace evaluation:
● SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
● Drive is accelerated beyond the SLS limit (time axis from approx. -800 ms)
● Exceeding the limit is recognized (time axis 0 ms)
● Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
● Fault response STOP B is initiated (time axis 0 ms; see bit "STOP A or B active" and
"SS1 active")
● Drive is decelerated to a standstill (see orange curve of r9714[0])
● Standstill reached (time axis from approx. 600 ms)
● STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this
point, the speed falls below the shutdown speed SS1 (p9560)
● SBR monitoring is activated after 250 ms
Not e
Time differences through internal c alculations
Small time differences (of the order of two to three Safety cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.