– "Forced dormant error detection (test stop) of the shutdown paths"
– "Forced dormant error detection (test stop) required"
– "PROFIsafe configuration" - only for control via PROFIsafe
– "Mechanics configuration"
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
You set the time after which the pulses must have been suppressed after initiating the
test stop (p9557) here.
You can set the interval for carrying out the forced checking procedure and test the
drive-integrated safety motion monitoring functions (p9559) here.
Select the parameters to be interconnected with the status "Shutdown path test
required" (r9723.0). One or more interconnections are possible, but not mandatory.
Click this button to open the "PROFIsafe Configuration" dialog box:
Enter the "PROFIsafe address" (p9610) of the drive in hexadecimal code here.
"Telegram configuration" (p60022) shows the currently parameterized PROFIsafe
telegram; "Safety parameterization" (p9611) shows the telegram currently used in the
Safety parameterization.
Click "Accept PROFIsafe telegram" to accept the currently parameterized PROFIsafe
telegram in the Safety parameterization.
Click "Close" to return to the "Safety Integrated" dialog box.
Click this button to open the "Mechanical System Configuration" dialog box:
Commissioning
6.7 Commissioning: Basic procedure
269