Maintenance
9.3 Safety faults
9.3.3

Acknowledging safety faults

Not e
A c knowledgment through Power Off/On
Safety faults can also be acknowledged (as with all other faults) by switching the drive unit
off and then on again (POWER ON).
If this action has not eliminated the fault cause, the fault is displayed again immediately after
power-up.
Acknowledgment via TM54F/CU310-2
Parameter p10006 "SI acknowledgment internal event input terminal" allows faults to be
acknowledged in the safety drives and with an F-DI of the TM54F or the CU310-2 itself.
The " s afe fault acknowledgment" mechanism functions as follows:
The fail-safe input F-DI on the TM54F or on the CU310-2 that was parameterized with the
function p10006 "Safety Integrated acknowledgment internal event input terminal", is
activated. In this way, faults that have occurred on the drives or on the TM54F are
acknowledged by means of a safe input signal. The falling edge at this input resets the
status "Internal Event" in the drives and, if used, in the TM54F or the CU310-2.
To prevent safety faults from being acknowledged unintentionally or incorrectly, the signal at
the F DI terminal, which was parameterized for acknowledgment purposes, must be at level
"0" in the quiescent state. To trigger the acknowledgment (falling edge at F DI), the signal
must first be set to "1" and then back to "0". If the required idle state is not reached, an alarm
is output.
After "safe fault acknowledgment", when using a TM54F, an acknowledgment must be made
at the Control Unit, in order to:
● Delete the TM54F faults from the fault buffer
● Reset the red Ready LED on the TM54F.
Acknowledgment via PROFIsafe
The higher-level controller sets the signal "Internal Event ACK" via the PROFIsafe telegram
(STW bit 7) separately for each drive object. A falling edge in this signal resets the status
"Internal Event" in the relevant drive, which therefore acknowledges the fault.
Faults in the drive objects (DOs) cannot be acknowledged by the higher-level controller in
the line-up but must instead be acknowledged separately for each individual drive object.
Ex tended acknowledgment
If STO or SS1 is selected/deselected (and p9507.0 = 1 are set), then the safety messages
are canceled automatically.
If, in addition to the "Basic Functions via terminals", the "Extended Functions" are also
enabled, then acknowledgment is also possible by selecting/deselecting STO via PROFIsafe
or terminals at the TM54F or at the CU310-2.