9.2 Note regarding firmware update

9.2
Note regarding firmware update
Danger to life on a f irmware update without POWER ON and acceptance t est
If the message A01007 "POWER ON required for DRIVE-CLiQ component" appears after a
firmware update, death or serious injury can be caused if a person enters the danger zone
of the motors.
• Then perform a partial acceptance test.
• Do not enter the danger zone of the motor until the acceptance test has been
Danger to life due t o unwanted motion when c hanging c omponents without function t est
After a component replacement, connections or functions can be defective so that death or
serious injury can result if a person enters the danger zone of the motors.
• Perform a POWER ON before resuming operation.
• After component replacement, always run a simplified function test.
364
WA RNING
successfully completed.
WA RNING
You can find more detailed information in the chapters "Test scope for specific
measures (Page 407)" and "Acceptance tests (Page 420)".
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6