A.3 Acceptance tests (recommendations)
N o .
r9722.12 (SDI positive active) or r9722.13 (SDI negative active)
Select SDI positive or SDI negative
Note: The parameterized SDI monitoring is already active for motion monitoring without selection.
Switch-on the drive and traverse in the negative or positive direction of rotation
Check whether the drive is moving, and after the SDI tolerance (p9564/9364) has
been exceeded that it is decelerated to a standstill along the OFF3 ramp
Check whether the following safety messages are pending:
C01716 (0), C30716 (0); tolerance for SDI exceeded in positive direction or
C01716 (1), C30716 (1); tolerance for SDI exceeded in negative direction
C01708, C30708 (STOP C initiated)
4.
Analyze trace:
As soon as r9713[0] leaves the SDI tolerance window, a safety message becomes
active (r9722.7 = 0).
STOP C is initiated as a consequence.
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Deselect SDI and safely acknowledge safety messages Initiate a POWER ON or a warm restart for motion monitor-
ing functions without selection.
Check whether the drive is running with the setpoint again
No safety faults, alarms and messages (r0945[0...7], r2122[0...7], r9747[0...7]) at the
drive and TM54F (if one is being used)
7.
Repeat points 1 to 6 for the opposite direction.