● If you have parameterized the forced dormant error detection (test stop) for POWER ON,
you can still initiate a forced dormant error detection (test stop) at any time through the
application.
● If the automatically initiated function cannot be correctly completed as a result of a
problem (e.g. communication failure), then after the problem has been resolved, the
function is automatically restarted.
● After the forced dormant error detection (test stop) has been successfully executed, the
converter goes into the "Ready" state.
● Timer p9659 is automatically reset as a result of the forced dormant error detection (test
stop).
● The automatic forced dormant error detection (test stop) for POWER ON does not
influence the Safety Integrated functions.
Not e
Res etting t he timer of the basic f unctions
• If the Extended Functions and the associated forced dormant error detection (test stop)
are used at the same time, the timer of the Basic Functions is also reset.
Discrepancy is not checked at the terminals used to select the Basic Functions as long as
STO is set by the Extended Functions. This means that the forced dormant error
detection (test stop) of the basic functions must be performed by the Extended Functions
without simultaneous selection of STO or SS1. It is otherwise not possible to verify the
correct control through the terminals.
• The timer is also reset if you first select "Change settings" and then "Activate settings" in
the start screen of the configuration in STARTER.
4.1.6

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List M anual)
• 2800
• 2802
• 2890
• 2891
• 2900
• 2901
• 2902
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
SI Basic Functions - Parameter manager
SI Basic Functions - Monitoring functions and faults/alarms
SI TM54F - Overview
SI TM54F - Parameter manager
SI TM54F - Basic Functions control interface (p9601.2/3 = 0, p9601.6 = 1)
SI TM54F - Basic Functions Safe State selection
SI TM54F - Basic Functions assignment (F-DO 0 ... F-DO 3)
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
79