Select SDI positive or SDI negative
Note: The parameterized SDI monitoring is already active for motion monitoring without selection.
Switch-on the drive and traverse in the negative or positive direction of rotation
Check whether the drive is moving, and after the SDI tolerance (p9564) has been
exceeded that it is decelerated along the OFF3 ramp before STOP A becomes active
Check whether the following safety messages are pending:
C01716 (0), C30716 (0); tolerance for SDI exceeded in positive direction or
C01716 (1), C30716 (1); tolerance for SDI exceeded in negative direction
C01701, C30701 (STOP B initiated)
C01700, C30700 (STOP A initiated)
4.
Analyze trace:
As soon as r9713[0] leaves the SDI tolerance window, a safety message becomes
active (r9722.7 = 0).
STOP B is initiated as a consequence (with subsequent stop STOP A)
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Deselect SDI and safely acknowledge safety messages Initiate a POWER ON or a warm restart for motion monitor-
ing functions without selection.
No safety faults, alarms and messages (r0945[0...7], r2122[0...7], r9747[0...7]) at the
drive and TM54F (if one is being used)
Acknowledge switch-on inhibit and run the drive
Check whether the drive is moving
7.
Repeat points 1 to 6 for the opposite direction.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6