4.9.2

Clean Power version with integrated Line Harmonics Filter (option L01)

Description
Line Harmonics Filter compact reduce the converter's low-frequency line harmonic to a level
that complies with standard EN 61000-2-4, Class 2 and correspond to IEEE 519:1992.
Installation location, total width and total weight for Option L01
The Line Harmonics Filter compact is installed fully wired in an auxiliary cabinet. A 400 mm
or 600 mm wide cabinet is used depending on the rated power. This therefore increases the
total width and the total weight of the cabinet.
Table 4- 35
6SL3710-1PE32-1AA0
6SL3710-1PE32-5AA0
6SL3710-1PE33-0AA0
6SL3710-1PE33-7AA0
6SL3710-1PE34-6AA0
6SL3710-1PE35-8AA0
6SL3710-1PE36-6AA0
6SL3710-1PE37-4AA0
Line system configurations
The Line Harmonics Filter compact may be connected to grounded TN/TT line supplies or
non-grounded IT line supplies according to IEC 60364-1.
Restrictions
Note
Relative short-circuit power RSC
The relative short-circuit power (RSC) of the supply system must be at least equal to the
value of RSC = 10.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Total width and total weight for Option L01
Article number
Converter rated power
3-phase 380 VA C -10% to 415 V +10% at 50 Hz
3-phase 380 V AC -10% to 415 V +10 % at 60 Hz
Width of the supple-
[kW]
mentary cabinet
Line voltage
110
132
160
200
250
315
355
400
Electrical installation
4.9 Other connections
Weight of the supple-
mentary cabinet
[mm]
400
400
400
400
400
600
600
600
[kg]
460
460
460
460
460
600
600
750
105