Siemens Sinamics G120P Operating Instructions Manual page 438

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Alarms, faults and system messages
9.3 Alarms
Emptying the alarm buffer: Alarm history
The alarm history traces up to 56 alarms.
The alarm history only takes alarms that have been removed from the alarm buffer. If the
alarm buffer is completely filled - and an additional alarm occurs - then the converter shifts all
alarms that have been removed from the alarm buffer into the alarm history. In the alarm
history, alarms are also sorted according to the "alarm time received", however, when
compared to the alarm buffer, in the inverse sequence:
● The youngest alarm is in index 8
● The second youngest alarm is in index 9
● etc.
Figure 9-4
Any alarms that have not been removed remain in the alarm buffer. The converter sorts the
alarms and closes gaps between the alarms.
If the alarm history is filled up to index 63, each time a new alarm is accepted in the alarm
history, the oldest alarm is deleted.
438
Shifting alarms that have been removed into the alarm history
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A

Advertisement

Table of Contents
loading

Table of Contents