Procedure
Proceed as follows to extend a telegram:
1. Use STARTER or the IOP to set parameter p0922 = 999.
2. Set parameter p2079 to the appropriate value of the corresponding telegram.
3. Interconnect additional PZD send words and PZD receive words with signals of your
choice via parameters r2050 and p2051.
Parameter
p0922
p2079
r2050[0...11]
p2051[0...11] PROFIdrive PZD send word
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller. For further information refer to the function block diagrams 2468 and 2470 of the
List Manual.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Description
PROFIdrive telegram selection
999:
Free telegram (message frame) configuration
PROFIdrive PZD telegram selection extended
1:
Standard telegram 1, PZD-2/2
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
PROFIdrive PZD receive word
Connector output to interconnect the PZD (setpoints) in the word format received
from the PROFIdrive controller.
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller.
6.5 PROFIdrive profile for PROFIBUS and PROFINET